AHU Sequence of Operations:
START SEQUENCE:
Step 1: Confirm no fire alarm active
Step 2: Open outside air damper → wait 30 seconds
Step 3: Start supply air fan → confirm run feedback within 5 seconds
If no feedback in 5 seconds → raise fault alarm, do not proceed
Step 4: Enable chilled water valve PID control
Step 5: Enable heating valve PID control
Step 6: Start return air fan
RUNNING:
Control supply air temperature at 16°C via CHW valve PID
Control space temperature at 24°C
Monitor CO2 → adjust fresh air damper via DCV logic
Monitor filter DP → alarm if above limit
STOP SEQUENCE:
Step 1: Close chilled water valve fully
Step 2: Stop supply air fan
Step 3: Stop return air fan
Step 4: Close outside air damper after 60 seconds
FIRE MODE:
Immediate stop on fire alarm signal
All dampers close
Manual restart required — no auto restart on fire
SOO అనేది English language description.
FBD అనేది అదే logic యొక్క visual drawing.
Controller అనేది దానిని run చేసే machine.
SOOను BMS design engineer వ్రాస్తారు. FBDని SOO నుండి program చేస్తారు. Commissioning రెండూ realityకి match అవుతాయని verify చేస్తుంది.