In a pharma lab in Bangalore, seven gas cylinders were being watched by one field engineer walking around with a pen and paper. No alerts. No screen. No alarm. Just a guy checking a dial. We changed that — completely.
7 cylinders · 4 oxygen + 3 CO₂ · Bangalore · 2025
Download the Full Case Study →This challenge was hidden but very important.
Each pressure transmitter on the cylinder sends a 4–20 mA current signal. That is the raw signal travelling from the transmitter to the controller panel.
Now here is the important part.
Our controller sequence program is written using voltage values to calculate and display the pressure. This means the controller does not directly understand milliamps — it needs the value in volts to do its job correctly.
So inside the controller, we convert the incoming 4–20 mA signal into 2–10V. The controller then reads that 2–10V value, runs it through the sequence logic, and displays the correct pressure reading on the HMI screen.
The sequence is simple —
Pressure transmitter sends 4–20 mA → signal enters the controller → controller converts 4–20 mA to 2–10V → sequence program reads the voltage → accurate pressure value displayed on HMI screen.
The result:
Inside the full case study, you'll see:
| Year | Milestone |
|---|---|
| Phase 1 | Site survey, sensor selection, and panel design for 7-cylinder setup |
| Phase 2 | Decision made to use 4–20 mA output on all 7 pressure transmitters and convert to 2–10V at the panel for accuracy |
| Phase 3 | Installation of 7 pressure transmitters on O₂ and CO₂ cylinders |
| Phase 4 | Panel fabrication — Controller + HMI panel (Panel 1) and 16UI/8UO IP I/O panel (Panel 2) |
| Phase 5 | Modbus RTU connection attempted, signal interference and data errors identified |
| Phase 6 | Protocol switched to Modbus TCP/IP, clean and accurate data confirmed across both panels |
| Phase 7 | Four-level setpoint logic programmed (50/70/90/110) for all 7 cylinders, hooter wired and tested |
| Phase 8 | BMS graphics built on 10-inch HMI, full system commissioned and handed over to client |
See how EnSmart helped Syngene Biotech deliver this project — full methodology, system architecture, and measurable outcomes inside the PDF.
Download PDF →The Syngene Biotech story is simple.
A pharma lab had seven critical gas cylinders. They were being watched by one person, with one pen, on a schedule. When that person went home, the cylinders were alone.
We came in and changed that completely.
We used 4–20 mA sensors and converted the signal properly to 2–10V at the panel — because direct voltage transmission is unreliable over distance and in noisy environments. We built two panels — one for control, one for field I/O — and connected them cleanly using Modbus TCP/IP after proving that Modbus RTU could not handle the site conditions. We programmed four alarm levels per cylinder so the team always has time to respond before a real crisis. We built BMS graphics on a 10-inch screen so any operator can see the full picture in seconds.
Before us — one man, seven cylinders, a pen.
After us — one screen, seven cylinders, zero guessing.
That is what we do at Ensmart.